Home Standby - 8 kW - 10 kW - 14 kW
|
GENERATOR |
Model 05501 (8 kW) |
Model 05502 (10 kW) |
Model 05503 (14 kW) |
|
Rated Maximum Continuous Power Capacity (LP) |
8,000 Watts* |
10,000 Watts* |
14,000 Watts* |
|
Rated Maximum Continuous Power Capacity (NG) |
7,000 Watts* |
9,000 Watts* |
13,000 Watts* |
|
Rated Voltage |
120/240 |
120/240 |
120/240 |
|
Rated Maximum Continuous Load Current 120 Volts 240 Volts |
66.6 LP/58.3 NG 33.3 LP/29.2 NG |
83.3 LP/75.0 NG 41.6 LP/37.5 NG |
116.6 LP/108.3 NG 58.3 LP/54.2 NG |
|
Total Harmonic Distortion |
Less than 5% |
Less than 5% |
Less than 5% |
|
Main Line Circuit Breaker |
35 Amp |
45 Amp |
60 Amp |
|
Phase |
1 |
1 |
1 |
|
Number of Rotor Poles |
2 |
2 |
2 |
|
Rated AC Frequency |
60Hz |
60Hz |
60Hz |
|
Power Factor |
1 |
1 |
1 |
|
Battery Requirement (not included) |
Group 26 12 Volts and 350 Cold-cranking Amperes Minimum |
Group 26 12 Volts and 525 Cold-cranking Amperes Minimum |
Group 26 12 Volts and 525 Cold-cranking Amperes Minimum |
|
Unit Weight |
336 Pounds |
375 Pounds |
425.5 Pounds |
|
Dimensions (L” x W” x H”) |
48 x 25 x 29 |
48 x 25 x 29 |
48 x 25 x 29 |
|
Sound output in dB(A) at 23 ft. with generator operating at normal load |
62 |
63 |
66 |
|
ENGINE |
Model 05501 (8 kW) |
Model 05502 (10 kW) |
Model 05503 (14 kW) |
|
Type of Engine |
GENERAC OHVI |
GENERAC OHVI V-TWIN |
GENERAC OHVI V-TWIN |
|
Number of Cylinders |
1 |
2 |
2 |
|
Rated Horsepower |
14.8 @ 3,600 rpm |
18 @ 3,600 rpm |
32 @ 3,600 rpm |
|
Displacement |
410cc |
530cc |
992cc |
|
Cylinder Block |
Aluminum w/Cast Iron Sleeve |
Aluminum w/Cast Iron Sleeve |
Aluminum w/Cast Iron Sleeve |
|
Valve Arrangement |
Overhead Valve |
Overhead Valve |
Overhead Valve |
|
Ignition System |
Solid-state w/Magneto |
Solid-state w/Magneto |
Solid-state w/Magneto |
|
Governor System |
Mechanical |
Electronic |
Electronic |
|
Compression Ratio |
8.6:1 |
9.5:1 |
9.5:1 |
|
Starter |
12 Vdc |
12 Vdc |
12 Vdc |
|
Oil Capacity Including Filter |
Approx. 1.5 Qts. |
Approx. 1.7 Qts. |
Approx. 1.7 Qts. |
|
Operating RPM |
3,600 |
3,600 |
3,600 |
|
Fuel Consumption Natural Gas cu.ft./hr. 1/2 Load Full Load Liquid Propane ft3/hr (gal/hr) 1/2 Load Full Load |
77 139 34 (0.94) 62 (1.68) |
102 156 46 (1.25) 70 (1.93) |
156 220 58 (1.56) 84 (2.30) |
|
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 11 to 14 inches of water column for LP gas |
|||
|
CONTROLS |
|
|
2-Line Plain Text LCD Display (10 & 14 kW) |
Simple user interface for ease of operation |
|
Mode Switch -Auto |
Automatic Start on Utility failure. 7 day exerciser |
|
-Off |
Stops unit. Power is removed. Control and charger still operate. |
|
-Manual/Test (start) |
Start with starter control, unit stays on. If utility fails, transfer to load takes place. |
|
Engine Start Sequence |
Cyclic cranking: 7 sec. on, 7 rest (90 sec. maximum duration) |
|
Engine Warm-up |
10 seconds |
|
Engine Cool-Down |
1 minute |
|
Starter Lock-out |
Starter cannot re-engage until 5 sec. after engine has stopped. |
|
2.5 Amp Timed Trickle Battery Charger |
Standard |
|
Automatic Voltage Regulator w/Overvoltage Protection |
Standard |
|
Automatic Low Oil Pressure Shutdown |
Standard |
|
Overspeed Shutdown |
Standard, 72Hz |
|
High Temperature Shutdown |
Standard |
|
Overcrank Protection |
Standard |
|
Safety Fuse |
Standard |
Home Standby - 8 kW - 10 kW - 14 kW
|
TRANSFER SWITCH & PRIORITY LOAD CENTER |
Model 05501 (8 kW) |
Model 05502 (10 kW) |
Model 05503 (14 kW) |
|
No. of Poles |
2 |
2 |
2 |
|
Current Rating (amps) |
100 |
100 |
100 |
|
Voltage Rating (VAC) |
250 |
250 |
250 |
|
Utility Voltage Monitor (fixed) -Pick-up -Dropout |
75% 65% |
75% 65% |
75% 65% |
|
Return to Utility |
approx. 13 sec. |
approx. 13 sec. |
approx. 13 sec. |
|
Exerciser weekly for 12 minutes |
Standard |
Standard |
Standard |
|
UL Listed |
Standard |
Standard |
Standard |
|
Dimensions (H” x W” x D”) |
26.5 x 12.5 x 7 |
26.5 x 12.5 x 7 |
26.5 x 12.5 x 7 |
|
Total of Pre-wired Circuits No. 15A 120V No. 20A 120V No. 20A 240V No. 30A 240V No. 40A 240V No. 50A 240V |
8 5 1 - 1 - - |
10 3 3 1 1 - - |
14 4 4 1 - 1 1 |
|
Circuit Breaker Protected Available RMS Symmetrical Fault Current @ 250 Volts |
10,000 |
10,000 |
10,000 |
Transfer Switch Features
• Electrically operated,
mechanically-held contacts for fast, positive connections.
• Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA 1 (indoor rated) enclosure is standard on the 100 amp switch.