Home Standby - 8 kW - 10 kW - 14 kW

GENERATOR

Model 05501 (8 kW)

Model 05502 (10 kW)

Model 05503 (14 kW)

Rated Maximum Continuous Power Capacity (LP)

8,000 Watts*

10,000 Watts*

14,000 Watts*

Rated Maximum Continuous Power Capacity (NG)

7,000 Watts*

9,000 Watts*

13,000 Watts*

Rated Voltage

120/240

120/240

120/240

Rated Maximum Continuous Load Current

120 Volts

240 Volts

66.6 LP/58.3 NG

33.3 LP/29.2 NG

83.3 LP/75.0 NG

41.6 LP/37.5 NG

116.6 LP/108.3 NG

58.3 LP/54.2 NG

Total Harmonic Distortion

Less than 5%

Less than 5%

Less than 5%

Main Line Circuit Breaker

35 Amp

45 Amp

60 Amp

Phase

1

1

1

Number of Rotor Poles

2

2

2

Rated AC Frequency

60Hz

60Hz

60Hz

Power Factor

1

1

1

Battery Requirement (not included)

Group 26 12 Volts and 350 Cold-cranking Amperes Minimum

Group 26 12 Volts and 525 Cold-cranking Amperes Minimum

Group 26 12 Volts and 525 Cold-cranking Amperes Minimum

Unit Weight

336 Pounds

375 Pounds

425.5 Pounds

Dimensions (L” x W” x H”)

48 x 25 x 29

48 x 25 x 29

48 x 25 x 29

Sound output in dB(A) at 23 ft. with generator operating at normal load

62

63

66

ENGINE

Model 05501 (8 kW)

Model 05502 (10 kW)

Model 05503 (14 kW)

Type of Engine

GENERAC OHVI

GENERAC OHVI V-TWIN

GENERAC OHVI V-TWIN

Number of Cylinders

1

2

2

Rated Horsepower

14.8 @ 3,600 rpm

18 @ 3,600 rpm

32 @ 3,600 rpm

Displacement

410cc

530cc

992cc

Cylinder Block

Aluminum w/Cast Iron Sleeve

Aluminum w/Cast Iron Sleeve

Aluminum w/Cast Iron Sleeve

Valve Arrangement

Overhead Valve

Overhead Valve

Overhead Valve

Ignition System

Solid-state w/Magneto

Solid-state w/Magneto

Solid-state w/Magneto

Governor System

Mechanical

Electronic

Electronic

Compression Ratio

8.6:1

9.5:1

9.5:1

Starter

12 Vdc

12 Vdc

12 Vdc

Oil Capacity Including Filter

Approx. 1.5 Qts.

Approx. 1.7 Qts.

Approx. 1.7 Qts.

Operating RPM

3,600

3,600

3,600

Fuel Consumption

Natural Gas cu.ft./hr.

1/2 Load

Full Load

Liquid Propane ft3/hr (gal/hr)

1/2 Load

Full Load

77

139

34 (0.94)

62 (1.68)

102

156

46 (1.25)

70 (1.93)

156

220

58 (1.56)

84 (2.30)

Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 11 to 14 inches of water column for LP gas

CONTROLS

2-Line Plain Text LCD Display (10 & 14 kW)

Simple user interface for ease of operation

Mode Switch

-Auto

Automatic Start on Utility failure. 7 day exerciser

-Off

Stops unit. Power is removed. Control and charger still operate.

-Manual/Test (start)

Start with starter control, unit stays on. If utility fails, transfer to load takes place.

Engine Start Sequence

Cyclic cranking: 7 sec. on, 7 rest (90 sec. maximum duration)

Engine Warm-up

10 seconds

Engine Cool-Down

1 minute

Starter Lock-out

Starter cannot re-engage until 5 sec. after engine has stopped.

2.5 Amp Timed Trickle Battery Charger

Standard

Automatic Voltage Regulator w/Overvoltage Protection

Standard

Automatic Low Oil Pressure Shutdown

Standard

Overspeed Shutdown

Standard, 72Hz

High Temperature Shutdown

Standard

Overcrank Protection

Standard

Safety Fuse

Standard

Home Standby - 8 kW - 10 kW - 14 kW

TRANSFER SWITCH & PRIORITY LOAD CENTER

Model 05501 (8 kW)

Model 05502 (10 kW)

Model 05503 (14 kW)

No. of Poles

2

2

2

Current Rating (amps)

100

100

100

Voltage Rating (VAC)

250

250

250

Utility Voltage Monitor (fixed)

-Pick-up

-Dropout

75%

65%

75%

65%

75%

65%

Return to Utility

approx. 13 sec.

approx. 13 sec.

approx. 13 sec.

Exerciser weekly for 12 minutes

Standard

Standard

Standard

UL Listed

Standard

Standard

Standard

Dimensions (H” x W” x D”)

26.5 x 12.5 x 7

26.5 x 12.5 x 7

26.5 x 12.5 x 7

Total of Pre-wired Circuits

No. 15A 120V

No. 20A 120V

No. 20A 240V

No. 30A 240V

No. 40A 240V

No. 50A 240V

8

5

1

-

1

-

-

10

3

3

1

1

-

-

14

4

4

1

-

1

1

Circuit Breaker Protected

Available RMS Symmetrical

Fault Current @ 250 Volts

10,000

10,000

10,000

Transfer Switch Features

• Electrically operated,

mechanically-held contacts for fast, positive connections.

• Rated for all classes of load, 100% equipment rated, both inductive and resistive.

• 2 pole, 250 VAC contactors.

• 160 millisecond transfer time.

• Dual coil design.

• Main contacts are silver plated or silver alloy to resist welding and sticking.

• NEMA 1 (indoor rated) enclosure is standard on the 100 amp switch.

 

Double D Electrical, Inc.